DDAU3 Data acquisition
DDAU3: data acquisition systems by Brüel & Kjær Vibro for data acquisition.
This series on the Brüel & Kjær Vibro site (opens in a new tab)
Models in the series
One column per model: what differs between the models of the series.
| Parameter | DDAU3 eli-m-33e0d24600a030d6a1b82720 |
|---|---|
| Number of measurement channels | 12 |
| Status | Active |
The industries we serve
Frequently asked questions
Answers to the most common questions about our products and services
The page lists 12 dynamic channels, four speed/DC inputs and eight 4–20 mA process inputs. These groups serve different functions.
The manufacturer defines 80 kHz as the dynamic-channel frequency-range limit. Sampling rate is a different specification; the two must not be substituted.
Yes. The manufacturer specifies integration with SCADA, PLC and OSIsoft PI systems.
Yes. Its internal storage retains data when the network connection is inactive.
The August 2026 data sheet specifies 204.8 kHz for AC/DC channels, 8 kHz for Speed/DC inputs used as DC channels, and 4 kHz for 4–20 mA inputs. Bandwidth is separate; the dynamic-channel 80 kHz bandwidth is not its sample rate.
No. State-dependent limits can change according to value ranges of other descriptors. Define operating states, thresholds and time hysteresis explicitly; connecting a sensor alone does not define the alarm policy.
Get a quote or advice
Tell us what you need and an engineer will come back to you.